How to size a grow room dehumidifier

How to Size a Dehumidifier for a Grow Room: Use Your Setpoint, Not the Label

How to Size a Dehumidifier for a Grow Room: Use Your Setpoint, Not the Label

A Quest 506 says 500 on the box. That is pints per day at 80°F and 60% relative humidity. Drop the room to 75°F and 50%, which is closer to where most flower rooms sit at lights-off, and the same unit is rated at 320 pints per day on Quest's own spec page. That gap is why so many rooms that were "sized right" on paper still climb past 60% RH an hour after the lights go out.

Here is the short version of how to size a dehumidifier for a grow room:

  1. Find how many gallons of water go into the room per day at peak (late flower).
  2. Subtract only the water that leaves the room as liquid, such as runoff piped to a drain outside.
  3. Multiply the rest by 8 to get pints per day. That is your moisture load.
  4. Add headroom. We use 20 to 25%.
  5. Pick units using their capacity at your actual setpoint, not the 80°F/60% rating.

The rest of this guide walks through each step with real numbers, then shows how the Quest and Anden units we carry stack up once you derate them. If a cheaper or smaller unit covers your room, we will say so. Want the math done for you? Try our grow room dehumidifier calculator.

Start with water, not square feet

A sealed grow room is close to a closed loop. Water goes in through the irrigation line, plants move it through their leaves, and it ends up in the air. Quest calls this the "water in, water out" starting point for sizing, and notes that it is a simplification. It is still the best place to start because you already know the number. You mix it every day.

How much of that water actually ends up as vapor? Dehumidifier Corporation of America puts it at about 97% of the water plants receive, with 8 pints in each gallon. In practice, treat almost all of the water that stays in the room as load. Water that sits in saucers, trays or open reservoirs evaporates too, so it is load as well. The only water you get to subtract is water that physically leaves the room as liquid: runoff plumbed to an outside drain, or a waste line from a recirculating system.

The square-foot rule is a cross-check, not a method

You will see canopy rules of thumb. Quest's own baseline is 0.5 to 2 pints of moisture per day for every square foot of canopy. That is a useful sanity check, but look at the spread. A 400 sq ft canopy could need anywhere from 200 to 800 pints per day by that rule. A fourfold range is not a purchase order. Your feed log narrows it down to one number.

Per-light rules have the same problem. "X pints per light" made more sense when every room ran the same 1,000 W fixtures. Today the wattage per fixture, the canopy under each one, and the irrigation strategy all vary, so the per-light number changes with them. If you know your water, you do not need a proxy for it.

Size for the peak week

Water use is not flat across a cycle. In a UC Davis greenhouse trial, plant water use ran about half the greenhouse evaporation rate when plants were small plugs, and about twice that rate near sale. Indoor crops follow the same shape: small plants drink little, and big plants in late flower drink the most. Size to the heaviest feed day you expect, not the cycle average. If you do not have a log yet, run your current room for a week in mid to late flower and record total gallons in and total gallons drained.

The label rating is measured in a room you do not run

Commercial grow dehumidifiers are advertised at 80°F and 60% RH. Quest calls that rating condition "an important baseline" but "not the most important number." The reason is simple physics. A refrigerant dehumidifier removes water by cooling air below its dew point. Warm, wet air at 80°F/60% has a high dew point, so the coil pulls a lot of water out of every cubic foot. Cooler, drier air has a lower dew point, so the same coil pulls out less. Quest's install team puts it plainly: "every dehumidifier's capacity drops with dew point," so size from actual performance at your setpoint, not the nameplate.

Here is what that looks like for three Quest units, using the manufacturer's published numbers at both conditions:

Unit Pints/day at 80°F/60% Pints/day at 75°F/50% Share of label Pints/kWh at 75°F/50%
Quest 225 225 130 58% 4.7
Quest 335 345 221 64% 6.0
Quest 506 500 320 64% 6.8

So at a typical flower setpoint, these units deliver roughly 58 to 64% of the number on the box. Efficiency drops too, which matters for your power bill (more on that below).

Anden's spec sheets for the A210V1, A320V1 and A710V1 list capacity at 80°F/60% only. That does not mean Anden units derate worse or better. It means you need to ask for the performance data at your setpoint before you finalize a count. Until you have it, a conservative planning assumption is that a refrigerant unit delivers about 60% of its 80/60 rating at 75°F/50%. That is our assumption based on the Quest curves above, not an Anden spec.

Pick your setpoint first

Because capacity depends on the room condition, you have to choose the condition before you can choose the unit. Quest's grower guidance lists 60 to 70% RH for vegetative growth and 40 to 60% RH in flower, with tighter control in late flower. If you steer by vapor pressure deficit, Michigan State floriculture specialist Erik Runkle describes 0.7 to 1.5 kPa as a moderate range that is a target for most plant growth applications. Whatever target you choose, look up capacity at the coolest, driest condition you plan to hold. For many flower rooms that is lights-off in late flower. If you run colder than 75°F at night, expect less capacity than the 75/50 column shows.

Home units use a different test again

If you are shopping residential portable units for a tent or a small room, there is a second trap. Since the DOE rules that took effect in June 2019, portable dehumidifiers are tested at 65°F rather than 80°F. Energy Vanguard founder Allison Bailes explains that under the newer test, a unit rated 30 pints per day under the old test would be rated at about 20. ENERGY STAR's conversion table puts an old 70-pint portable at roughly 40 to 45 pints under the new rating. The practical point: a residential "50 pint" label and a commercial "50 pint" label are not the same measurement. Compare units only within the same test standard, and ask for data at your conditions when you can.

Worked example: a 60-gallon flower room

Here is the full calculation for a sealed flower room. Swap in your own numbers.

  • Peak feed: 60 gallons per day in late flower.
  • Runoff: 15%, plumbed to a drain outside the room. That is 9 gallons that leave as liquid.
  • Water that stays in the room: 60 minus 9 = 51 gallons.
  • Vapor: 51 gallons at about 97% = 49.5 gallons.
  • Moisture load: 49.5 × 8 = about 396 pints per day.
  • Headroom: 396 × 1.25 = about 495 pints per day at the setpoint.

Why 25% headroom? Feeds creep up, filters load, a door gets propped open during a harvest, and a unit trips. Quest's install guidance also recommends keeping a modest capacity buffer for spikes and maintenance. Dehumidifier Corp suggests adding small fixed amounts for extra sources, such as 5 pints for people working in the room and 10 pints for ventilation in a humid climate. In a room this size those add-ons are small next to the plants, and the percentage headroom covers them.

Now pick hardware at 75°F/50%

Our target is about 495 pints per day at the setpoint. Here is what different Quest combinations deliver at 75°F/50%, using the published numbers from the table above:

Option Label total (80/60) Setpoint total (75/50) Meets 495?
1 × Quest 506 500 320 No, short about 175
2 × Quest 335 690 442 No, short about 53
4 × Quest 225 900 520 Yes
1 × Quest 506 + 1 × Quest 335 845 541 Yes
2 × Quest 506 1,000 640 Yes, with extra room to grow

Look at the first row. A grower who calculates 495 pints and buys one 500-pint unit has done the math right and still ends up about 35% short at lights-off. Look at the second row too. Two 335s total 690 on the label, comfortably over 495, and still come up short at the setpoint. It is an easy mistake to make, and it is not a math error. It is a units error.

Lights-off is the design hour

With lights on, your air conditioner is running hard to remove heat, and as a side effect its cold coil condenses some water out of the air. When the lights go off, the heat load disappears, the AC throttles back, and the plants keep transpiring. Quest notes that dehumidifiers work hardest with lights off, when the AC runs less and plants keep transpiring. That is the hour your dehumidifiers must carry the room alone, so size for it.

This is also why we do not take a large "AC credit" off the moisture load. Some sizing methods subtract part of the AC's moisture removal. That works during lights-on, but the AC is a poor dehumidifier exactly when you need one most. If your room has a dedicated system built to control humidity at night, use its published latent capacity. Otherwise, plan as if the dehumidifiers do the night shift alone.

One side effect to plan for: dehumidifiers add heat. In one Quest case study, dropping the setpoint from 57% to 50% RH raised the nighttime average from 63°F to 71°F, likely because the dehumidifier was running more often. If you want a real day-to-night temperature drop, you may need some nighttime cooling as well.

One big unit or several smaller ones

Once you know the pints, you still have to decide how to split them. Quest's guidance favors several mid-size units over one big one. A single large unit cycles on and off at low loads, which causes RH swings, while smaller units can be staged back as the load drops. Their install team adds that one big unit is a single point of failure, and cites four to six units as a practical range for many flower rooms.

The trade-offs are real, though:

  • More units means more circuits, more drains and more hanging points. Four Quest 225s is four condensate lines to keep clear.
  • Smaller units can be less efficient. At 75°F/50%, the Quest 225 is rated at 4.7 pints/kWh versus 6.8 for the 506 (table above). More on what that costs below.
  • Small rooms do not need four units. If your load at setpoint is 120 pints, one appropriately sized unit with a little headroom is fine. Redundancy matters most when a crop failure costs more than a second unit.

If you go with multiple units, do not wire them all to one on/off signal. Quest warns that tying every unit to one signal behaves like one oversized unit. Stagger the setpoints so one unit carries the base load and the others come on as RH climbs. A controller with a dedicated humidistat output, like the TrolMaster Hydro-X Humidistat Station, is one way to do that. The controller you already own may handle it too.

Placement and drains

Pints on paper only help if dry air reaches the canopy. Quest's field advice is to aim the discharge down aisles or over the canopy, avoid spots near a wall or directly under an AC register, and space units to match the room shape. Keep drains clear and level. Where gravity drainage is not possible, a pump such as the Quest condensate pump kit moves water to a drain. Do not let condensate go back into the room, or you are just cycling the same water.

Check amps and pints per kWh before you order

Two numbers decide whether your plan actually works in your building: current draw and efficiency.

Amps. Add up the amps for every unit on the circuit and confirm voltage before you order. Quest's install team says the same: confirm voltage and amperage before ordering. Published draws at 80°F/60% and 230 V include:

In the worked example, four Quest 225s draw about 22 A at 230 V, while a 506 plus a 335 draw about 17.5 A. That difference can decide whether you need a new circuit.

Pints per kWh. Efficiency is quoted at the same 80/60 condition as capacity, so compare like with like. At 80°F/60%, Quest lists 7.6, 8.2 and 9.2 pints/kWh for the 225, 335 and 506, and Anden lists 6.1, 6.0 and 6.35 pints/kWh for the A210V1, A320V1 and A710V1 (sources linked above). At your setpoint, all of these numbers drop.

Here is what efficiency means in money for the worked example. Removing about 396 pints per day at 75°F/50%:

  • Four Quest 225s at 4.7 pints/kWh use about 84 kWh per day.
  • A Quest 506 plus a Quest 335, sharing the load in proportion to capacity, use about 61 kWh per day.

That is about 23 kWh per day. At a hypothetical $0.15 per kWh, it comes to roughly $3.45 a day, or about $1,250 a year if the room runs year-round. The cheaper-to-buy option is not always the cheaper option to own. Run it with your own power rate.

Matching the load to real units

With your setpoint load in hand, this is how the units we carry line up. These are not the only good options. Other brands publish performance curves too, and the same derating logic applies to all of them.

  • Up to about 130 pints at setpoint: one Quest 225. It is also the building block for larger rooms that want many small, staged units. For a small room or tent where a commercial unit is overkill, a portable such as the Active Air 110-pint dehumidifier may be enough. Check which test standard its rating uses.
  • Around 200 to 450 pints at setpoint: one or two Quest 335 units (221 pints each at 75/50), or Anden's A210V1 and A320 (277 V version), sized with setpoint data from Anden or the planning assumption above.
  • Larger flower rooms: multiples of the Quest 506 (320 pints at 75/50) or the Anden A710 (710 pints at 80/60), mixed with a smaller unit so you can trim capacity as the load changes.

If you send us your peak feed, runoff, setpoint and available circuits, we can run the numbers with you. The math is the same whether you buy from us or not.

A one-page sizing worksheet

Copy this into a notebook or spreadsheet. It is the same calculation as above, without the commentary.

  1. Peak gallons in per day (late flower): ______
  2. Gallons leaving the room as liquid (runoff to an outside drain): ______
  3. Gallons staying in the room (line 1 minus line 2): ______
  4. Moisture load in pints/day (line 3 × 0.97 × 8): ______
  5. Design load (line 4 × 1.20 to 1.25): ______
  6. Lights-off setpoint (temperature and RH): ______
  7. Each unit's capacity at that setpoint (from the manufacturer's curve or spec page): ______
  8. Units needed (line 5 divided by line 7, rounded up): ______
  9. Total amps and available circuits: ______

If line 7 is missing for a unit, get it from the manufacturer before you buy. That one number is the difference between a room that holds 50% at lights-off and one that does not.

Frequently asked questions

How many pints per day does my grow room need?

Take your peak daily gallons, subtract water that drains out of the room as liquid, and multiply the rest by about 0.97 and then by 8. That is pints per day. Add 20 to 25% headroom, then choose units by their capacity at your actual setpoint. A sealed room using 60 gallons a day with 15% runoff to drain needs about 400 pints per day before headroom.

Is there a rule for pints per light or per square foot?

Rules exist, but they are wide. Quest's canopy baseline is 0.5 to 2 pints per square foot per day, a fourfold range. Per-light rules vary with fixture wattage and canopy size. Use them only to sanity-check a number you calculated from your water.

Can a dehumidifier be too big for a grow room?

Yes. A single oversized unit short-cycles at low loads, which causes RH swings. If you need extra capacity, split it across several staged units rather than one large one, so some units can sit idle when the load is light.

Why is my dehumidifier not keeping up at lights-off?

Usually there are two reasons together. First, the AC removes much less moisture once the lights go off, while the plants keep transpiring. Second, the unit was sized from its 80°F/60% rating, and at a 75°F/50% setpoint it may deliver only about 58 to 64% of that. Check the unit's capacity at your real setpoint, and check for clogged filters and blocked airflow.

Does my air conditioner count toward dehumidification?

During lights-on, partly. During lights-off, very little, because the AC barely runs. Size the dehumidifiers to handle the lights-off load on their own unless you have a system built specifically to control humidity at night.